Page 283 - HVAC Pump Handbook
P. 283

Rishel_CH10.qxd  21/4/06  6:20 PM  Page 280




                                   Basics of Pump Application for HVAC Systems

                    280   The HVAC World

                    high as 1210 or 1840 rev/min provides an additional load factor.
                    Reiterating, in all this work, the maximum pump horsepower must be
                    calculated to ensure that the motor and the variable-speed drive are
                    not overloaded. Likewise, it is wise to verify that the pump manufac-
                    turer approves the operation of the pump at the proposed speed.



                    10.3.1 Variable-speed pump operation
                    Most variable-speed pump operations in HVAC water systems track a
                    system head curve as was defined by Eq. 9.3 in the previous chapter.
                    Both the flow and head vary with this curve. As will be seen in the
                    chapters on chilled and hot water distribution, a remote differential
                    pressure transmitter is utilized to cause the pump head and flow to
                    follow the system head curve or the desirable point in the system
                    head area.
                      There are other useful variable-speed operations in the HVAC field,
                    such as constant flow, variable head. In this case, the pump flow
                    remains constant while the pump head and speed change with system
                    conditions. Typical of this is constant flow through a chiller condenser.
                    The head increases as more chillers are placed in operation as shown
                    in Fig. 10.4. The flow is a constant 2000 gal/min as the system head
                    increases and decreases. Such an operation can result in relatively
                    high pump efficiency, as shown in Fig. 10.5.
                      This figure describes the pump efficiency, as it cuts across the
                    curves of constant efficiency. In all variable-speed operations, this
                    should be observed to ensure that the pumps are operating at the best




                       80  1175 RPM
                                                 70%  75%  80%  83%

                       60  1000 RPM                             86%  87%  Bep curve
                      Pump head—ft.  40  800 RPM                             83%
                                                                          86%


                                                                             Individual
                                                                             efficiency
                       20                                                    lines of

                        0
                         0    400   800   1200   1600  2000  2400   2800  3200
                                          U.S. Gallons  per minute
                    Figure 10.4 Constant flow, variable head process.




                 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                            Copyright © 2006 The McGraw-Hill Companies. All rights reserved.
                             Any use is subject to the Terms of Use as given at the website.
   278   279   280   281   282   283   284   285   286   287   288