Page 156 - Handbook of Electrical Engineering
P. 156

TRANSFORMERS      139

           • AF AIR-FORCED:- Air forced cooling is arranged by using fans and trunking on the outside of
             the transformer. These can be applied to dry-type or liquid insulated transformers.

                 Transformers rated up to approximately 2.5 MVA are usually fitted with cooling tubes or tank
           mounted radiators. These units would typically feed low voltage switchboards. Between 2.5 MVA and
           15 MVA the use of tubes would be inadequate and tank mounted radiators would be necessary. Above
           about 10 MVA the radiators would be separately mounted from the tank and coupled by pipework.
                 The overall construction of oil and liquid filled transformers would be IP55 as defined
           in IEC60529.
                 Oil industry sites are often located in hostile environments which also have aggressive transport
           routes for the delivery of their equipment. It is therefore necessary to construct the windings and
           core components in such a manner that they can withstand impacts and rough handling during
           transportation to site. The windings should be robustly braced to ensure that they do not move during
           transportation.
                 Other variations including using water-cooling are possible but these are not commonly
           encountered.
                 The amount of heat typically dissipated from a liquid-immersed transformer is about 12.5 watts
           per square metre of surface area per degree C. If such a transformer is inside a room or module then
           this heat must be removed by changing the air regularly, or by the HVAC cooling system. The heat
           dissipation can also be calculated directly from the known efficiency of the transformer at full load.

                 Transformers are usually fitted with devices to indicate the temperature of liquid, windings
           and the core. These may be direct-reading thermometers, indirect resistance temperature detectors
           (RTDs) or thermocouples. Signals from these devices are used to trip the feeder switchgear in the
           event of excessive temperature.
                 Liquid-immersed transformers are fitted with special safety relays and devices to safeguard
           the unit from internal faults and explosions. Slowly generated faults tend to produce gas from the oil
           or liquid.

                 The gas accumulates in a special chamber which is fitted with two float switches, and these
           operate alarms and trips when the gas accumulates slowly or rushes in during internal explosions. This
           system is called a Buchholz relay, and is normally used only on transformers fitted with conservator
           tanks. Transformers below about 1600 kVA are often sealed type liquid-immersed units. Internal
           explosions are released by using a special blow-off valve. Often the space above the liquid level in
           this type of unit is filled with an inert gas such as nitrogen.
                 Reference 3 gives an excellent description of all the aspects of transformer design, testing
           and operation.


           6.5.1 Conservator and Sealed Type Tanks

           Conservator type transformers are fitted with an overhead tank which is approximately half full of
           the oil or liquid insulant. The overhead tank is allowed to breath to atmosphere as the liquid level
           varies with the average temperature inside the transformer. It breathes through a small vessel filled
           with silica gel which absorbs the water vapour that may pass into or out of the transformer.
   151   152   153   154   155   156   157   158   159   160   161