CABLES, WIRES AND CABLE INSTALLATION PRACTICES     191

           9.3 COMPOSITION OF POWER AND CONTROL CABLES

           The composition of a power cable is dependent upon the rated voltage at which it will be expected
           to operate continuously without breakdown.
                 IEC60038 gives the standard voltages for electrical equipment. However, for cables the AC rms
           voltages are defined for example in IEC60502, in terms of their line-to-earth and line-to-line values.

                 See Tables 9.6 and 9.7. Table 9.7 is derived from BS6622.
                 Note that occasionally u o is quoted as the value obtained by dividing u by 1.732 and rounding
           to one decimal place. u o is derived from IEC60038.

                 IEC60502 covers the construction and factory testing of polymeric solid insulated cables in
           the voltage range 1000 to 30,000 volts. IEC60183 gives guidance on the selection of cables for high
           voltage systems. BS6622 is similar to IEC60502 but is restricted to cables operating at voltages
           between 6600 and 33,000 volts, with screened XLPE or EPR insulation. BS5467 covers unscreened
           thermosetting insulated cables that operate between 1000 and 3300 volts; hence the standard is
           reasonably applicable to low voltage systems e.g. 380, 400, 415, 440, 600 and 750 volts (line to


                                Table 9.6.  IEC standard rated voltages of power cables
                           Line-to-earth  Line-to-line  Maximum value of the highest
                              voltage       voltage      system line-to-line voltage
                               u o            u                   u m
                                600         1,000                 —
                              1,800         3,000                3,600
                              3,600         6,000                7,200
                              6,000         10,000              12,000
                              8,700         15,000              17,500
                             12,000         20,000              24,000
                             18,000         30,000              36,000


                                Table 9.7.  UK standard rated voltages of power cables
                                Line-to-earth  Line-to-line  Maximum value of
                                voltage         voltage     the highest system
                                                            line-to-line voltage
                                                                ∗
                                    u o           u            u Note a)
                                                                m
                                    600          1,000            —
                                   3,800         6,600           (8,000)
                                   6,350        11,000          (13,200)
                                   8,700        15,000          (17,500)
                                  12,700        22,000          (26,400)
                                  19,000        33,000          (39,600)
                                Note a) This column is not shown in BS6622 but is included
                                      to be consistent with Table 9.6 where a 20% upward
                                      margin is added to u to obtain u m before rounding
                                      is applied.
                                Note b) A method of rounding numbers upwards or downwards
                                      is given in Appendix B of IEC60502.