272    HANDBOOK OF ELECTRICAL ENGINEERING































                                Figure 11.3  One-line diagram of faulted low voltage system.





















                                Figure 11.4 Equivalent circuit of faulted low voltage system.


                                          Table 11.2. Impedance data values
              Item         R1      X1        R2         X2        R3      X3      R4         X4
              T1                0.0333 pu  0.6 pu
                                             ∗
                                     ∗
              3c-240 mm 2                  0.01976   0.0146
              Cable C1                     0.1815 pu  0.1343 pu
                                                ∗
                                                          ∗
                                                                   ∗
                                                                          ∗
              T2                                                0.35 pu  3 pu
              Busbars                                                          0.000086   0.00044
                                                                                               ∗
                                                                                    ∗
              B1                                                               0.0444 pu  0.2273 pu
              ∗ per unit at 100 MVA base.