Page 311 - Handbook of Electrical Engineering
P. 311

FAULT CALCULATIONS AND STABILITY STUDIES     297




























                            Figure 11.14 One-line diagram of a two-platform power system.

                 The star and delta configurations use reactors that have lower reactances than the simple method
           of Figure 11.11. This will give rise to better stability in both the steady state and the transient state.
           In addition the AVR set-point circuits should not need to be modified.


           11.9.1 Worked Example


           Consider the systems shown in Figures 11.11 to 11.13. Assume that all the generators are rated at
           20 MVA, with sub-transient reactances of 0.15 pu and the main switchboard operates at 11 kV. The
           symmetrical making current duty of the switchboard is 30,000 amps. Ignore motor contribution in this
           example. Calculate the per-unit reactance X r required for each reactor in the three different systems.

           a) Case A: Simple system
              The 1 pu current of each generator is,

                                          S      20,000,000
                                    I 1 = √   = √           = 1049.8 amps
                                          3V      3 × 11,000

              The short-circuit current available from each generator is,

                                         E I 1   1.1 × 1049.8
                                    I fg =    =             = 7698.2 amps
                                         VX       1.0 × 0.15
                                            d
              Without reactors and with five generators operating the total fault current is

                                         I fa = 5 × 7698.2 = 38,491 amps

              which exceeds the duty of the switchgear by 8491 amps.
   306   307   308   309   310   311   312   313   314   315   316