296    HANDBOOK OF ELECTRICAL ENGINEERING






























              Figure 11.12  One-line diagram of a star-connected reactor system for reducing the fault level at the switchgear
              in the system.


























              Figure 11.13  One-line diagram of a delta-connected reactor system for reducing the fault level at the switchgear
              in the system.

              only using three circuit breakers in the existing switchgear, whereas the delta system needs six. This
              economises the modification of the existing switchgear in terms of cost and space, however, the star
              system requires a new but small switchboard for the common connections. This new switchboard
              could be fitted with load break switches instead of circuit breakers, with protection being given by
              the circuit breaker in the existing switchgear.