Page 348 - Handbook of Electrical Engineering
P. 348

PROTECTIVE RELAY COORDINATION      335

           to open the incomer and bus-section circuit breakers so that the fault does not develop and spread as
           a fire or blast along the busbars.


           12.6.2 Overcurrent Protection

           It is not normally necessary to provide overcurrent protection in the bus-section circuit because the
           presence of overcurrent, not caused by an in-zone fault, would be detected by an outgoing circuit
           relay. For the busbar to be overloaded the outgoing system must also be overloaded. Introducing an
           overcurrent relay in the bus-section circuit will add complication to the coordination of the incoming
           and outgoing relays, since a time margin is necessary between each relay. In systems where there
           are large induction motors the coordination can already be awkward to achieve.


           12.6.3 Undervoltage Protection

           If the busbars are being operated at an unusually low voltage then the consumers may attempt to
           consume their full power. If this happens they will take in more than their rated current, which is a
           potentially damaging condition. If the switchboard supplies one or more large induction motors then
           during their starting process they will draw a heavy current. Should the motor experience difficulty
           during starting then a prolonged period of high current will occur and this could cause a depression
           in the busbar voltage. Such a depression may adversely affect other consumers.
                 Undervoltage operation is undesirable and therefore a suitable relay (27) with a time delay is
           often used, especially in high voltage switchboards. A similar problem can arise with main generator
           switchboards. If a generator is suddenly tripped then the remaining generators must try and supply
           the load. Each of these generators will experience a sudden increase in current and a drop in terminal
           voltage. The load will react to the drop in voltage. The automatic voltage regulators will try and
           restore the voltage. If the load is predominately induction motors then they will all try and accelerate
           back to their normal speed. The acceleration will be accompanied by an increase in their reactive
           current which will aggravate the volt-drop and delay the voltage recovery. If the depression is more
           than at least 20% and lasts for more than 0.2 to 0.5 seconds then there is a risk that the system of
           induction motors will fail to recover, see also sub-section 7.6.1.
                 The (27) relays should have an adjustable voltage range to cover for the 80% voltage condition,
           typically 50% to 100%. The relay should have a time delay that is adjustable up to at least 0.5 second.
                 The relay may be set to trip all the outgoing circuits on its section of busbars. Alternatively
           a more selective method can be used in which the largest consumers are tripped initially. If the
           initial tripping fails to produce a good recovery then a second level of tripping may be used for the
           remaining consumers.
                 During the studies that are usually carried out for system stability, starting large motors, loosing
           a generator etc., a study of undervoltage (and overvoltage) should be included. Several scenarios
           should be considered so that a good compromise between voltage depression and its duration can be
           found for setting the (27) relays.
                 Undervoltage schemes are often included in the reacceleration control systems of individual
           motors or groups of motors. However, these are more appropriately considered in motor protection
           rather than busbar protection schemes.
   343   344   345   346   347   348   349   350   351   352   353