Page 382 - Handbook of Electrical Engineering
P. 382

370    HANDBOOK OF ELECTRICAL ENGINEERING

              per-unit or percentage factors that relate to the grid geometry. These are then used to scale down the
              GPR by simple multiplication. The mesh voltage E m is usually more of a constraint on the design
              than the step voltage E s . The IEEE80 standard provides graphs of E m and E s for different mesh
              configurations, (Figures B1 to B5 therein).
                    In Reference 3 a typical design of a grid of large area would be to bury it to about 0.5 m and
              choose each mesh in the grid to have sides of length about 5 or 6 m. This would give a good starting
              point for a series of calculations.



              13.3.5.4 Fault current entering the ground
              For most practical designs the calculation of a ‘single line-to-ground or L-G’ fault current should be
              adequate. Assume the fault occurs at the pole location and that the pole is at a long distance from
              the source of power. Assume for a simple example that the overhead line is a simple radial circuit
              fed only from one end, and that the line is furnished with an overhead earthing conductor. To be
              conservative assume that the earthing conductor is only bonded to the pole in question and to the
              neutral earthing point at the source end. The source is considered to be earthed through a neutral
              earthing resistor (NER) having a resistance R n .

                    The overhead earthing conductor will divert some of the L-G fault current from entering the
              ground at the foot of the pole. The extent of diversion will be in proportion to the impedance of the
              overhead line compared with that of the earth resistance path back to the source. The calculations
              required for determining the fault current and its diverted amounts are shown in Appendix H by way
              of an example, and Figure 13.12.

































                               Figure 13.12 Earthing circuit of an overhead transmission route.
   377   378   379   380   381   382   383   384   385   386   387