Page 384 - Handbook of Electrical Engineering
P. 384

372    HANDBOOK OF ELECTRICAL ENGINEERING

                    Cubicles and light duty terminal or junction boxes often use stainless steel or painted mild
              steel gland plates for receiving cable glands, occasionally brass plates are used for single-phase and
              DC cables. Stainless steel may also be used for special services. These plates are chosen to be
              between about 2 and 5 mm thick, to provide adequate rigidity and resistance to the ingress of dust
              and liquids, as defined for example in the international standard IEC60529, see also Chapter 10. The
              glands pass through plain or clearance holes and are secured by lock-nuts and spring washers on the
              inside surface. Since the entry is a plain hole with a painted surface, it is necessary to use earthing
              tabs. Each cable should have a tab and all the tabs should be bonded to a common earthing boss
              nearby. The tabs may be on either the outer or the inner surface, depending on the type of equipment
              and its environment. Care must be taken to ensure that water and other liquids cannot pass along the
              entry hole.
                    Casings and heavy-duty terminal boxes are often made of cast iron or fabricated from thick
              steel plates. Occasionally cast bronze may be used, in services offshore where sea water corrosion
              may be a problem. In these cases the entry is usually threaded. The gland is screwed into the threaded
              hole. A washer may be required between the outer surface of the box and the gland, to satisfy the
              requirements for ingress of liquids and particles, and for the hazardous area. When Ex (d) glands are
              used with Ex (d) boxes it is necessary to ensure that the prescribed number of threads on the gland
              enter the hole.
                    Most casings, terminal boxes and gland plates are provided with one or two earthing studs for
              bonding them to the earthing system. If a terminal box is cast integral with the frame or casing of a
              motor, a generator or other machine, then an earthing stud is not necessary at the box, but the frame
              will have one or two studs or bosses for the same purpose.



              13.4.3 Earthing Only One End of a Cable

              Multi-core cables used for control, instrumentation, computers and telecommunications carry very
              small currents in their conductors, when compared with power cables, and these currents feed into
              very sensitive electronic circuits. The system design of these electronic circuits must take account of
              interference that can be induced or circulated in the cable conductors. Screens are provided around
              groups of typically two, three or four conductors, which are mainly intended to discharge static charges
              that can otherwise accumulate and create noise or damage at the terminal equipment. Screens are
              also provided around all the conductors in the cable for a similar reason.

                    If a screen is earthed at both ends of its cable then a ‘stray’ current may be caused to flow in
              the screen. This is because the earth potential at each end of the cable may not be exactly the same or
              both zero. A few millivolts difference due to random stray currents, or worst still fault currents, in the
              local earth or steelwork is enough to cause difficulties with the electronic signals. The stray current
              flowing along the screen will magnetically induce currents into the core conductors. It is therefore
              common practice to earth the cable screens only at one end of the cable. The bonding of each screen
              is made at a specially designed ‘clean earth’ busbar mounted inside, for example, a control panel or
              marshalling box.
                    High voltage power cables that operate at voltages above about 3000 V are provided with
              graphite semiconducting screens at the surface of the conductor and on the outside surface of the
              insulation. The purpose of the screen around the conductor is to control the potential gradient, or
              electric stress, in the insulation that is close to the conductor. The high surface voltage is accompanied
   379   380   381   382   383   384   385   386   387   388   389