Page 462 - Handbook of Electrical Engineering
        P. 462
     UNINTERRUPTIBLE POWER SUPPLIES     451
           downstream device and the lower tolerance of the upstream device. If the two cascaded devices are
           of the same type, range of products from the same manufacturer, and similar shapes of curves then
           the margin of coordination can be relatively low. Often these cascaded devices are different, e.g.
           fuses upstream with circuit breakers downstream or vice versa, and their manufacturers are different.
           This will generally result in requiring a wider margin for coordination. A ‘rule-of-thumb’ guide can
           be based on the normal rated currents of these devices. For a good situation where the type of the
           two devices is the same, e.g. both are fuses or both are circuit breakers, the marginal factor should
           be no less than 2.5. For the poor situation with dissimilar devices the marginal factor may need to be
           at least 3.0. In the above discussion it is assumed that the protective devices do not have a definite
           minimum time at currents within the range of fault current being considered. This is a different
           situation from one in which the prospective fault currents are much greater than full-load currents,
           see sub-sections 7.7.5 and 7.7.6.
                 It should be noted that a UPS on an important plant, such as a production platform, is in
           a critical situation. It must function in a very reliable manner otherwise the cost of lost oil or gas
           production will be very high in relation to the cost of all the components in the UPS system that are
           unreliable. If the unreliability is due to poor coordinations of protective devices then the marginal
           factors described above may need to be reviewed, or better still applied in the early stages of the
           power system design.
                 Reference 1 gives a good description of the coordination of protective devices and their pro-
           tected equipment, a diagrammatic procedure and a worked example consisting of miniature circuit
           breakers and an upstream fuse in a 415 V three-phase system. See also sub-section 13.3.2 for a brief
           discussion on the use of a high impedance to earth a low-voltage emergency or drilling power system.
                 Reference 2 discusses the difficulties that can be experienced with coordinating cascaded
           protective devices, plus a comprehensive description of all aspects of NiCd charger-battery-inverter
           systems.
           17.1.3 Earth Fault Leakage Detection
           Short circuits often develop from faults of a leakage nature. It is therefore advisable to provide each
           sub-circuit with an earth leakage current relay or alarm unit, which has a sensitivity that adequately
           coordinates with other devices. Indeed this is a necessary requirement for sub-circuits that feed power
           to hazardous area equipment. The use of these earth leakage current relays and detectors will greatly
           increase the confidence that can be placed on the overall performance of the system of protective
           devices in the UPS.
           17.2 DC UNINTERRUPTIBLE POWER SUPPLIES
           A DC uninterruptible power supply is basically a battery bank and a charger. However, it differs
           from a simple battery and charger system that may be associated with starting diesel engines, or
           similar rugged functions, because the output voltage must be maintained within a close tolerance of
           the nominal DC voltage.
           DC uninterruptible power supplies are used for:
           • Closing and tripping of circuit breakers and contactors in switchboards.
           • Switchboard indicating lamps.





