Appendix C




           Numbering System for Protective

           Devices, Control and Indication Devices

           for Power Systems









           C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM
                DEVICES FOR POWER SYSTEM CIRCUITS

           The requirements for the different types of HV and LV circuits in a typical oil industry power system
           are summarised below. The IEEE device numbers commonly used in the oil industry are listed in
           sub-section C.2.
            1. Utility intake above 11 kV.
               25, 27, 51V, 51N, 86, 87.
            2. Unit transformer-generator intake above 11 kV.
               Primary circuit, see note 1.
               Secondary circuit 25, 26, 27, 32, 40, 46, 51V, 51G, 59, 64, 81, 86, 87.
            3. Switchgear busbar zone protection above 11 kV.
               86, 87 see note 2.
            4. Switchgear bus-section and bus-couplers above 11 kV.
               25, 27 see note 3, 86.
            5. Transformer feeders above 11 kV.
               Primary circuit, 23 see note 4, 49, 50, 51, 51N, 86, 87.
               Secondary circuit, 23 see note 4, 51G see note 5, 64 see note 6, 86.
            6. Unit transformer-motor feeders above 11 kV.
               Primary circuit, 23 see note 4, 26, 27, 59, 86, 87.
               Secondary circuit, 23 see note 4, 51G, 64, 87 see note 1.
               Motor, 25 see note 4, 26, 46, 49, 50, 51N, 87.
            7. Overhead line feeder above 11 kV.
               51, 51N, 86.