Page 588 - Handbook of Electrical Engineering
P. 588

CALCULATION OF VOLT-DROP IN A CIRCUIT CONTAINING AN INDUCTION MOTOR      581

                              Table G.1. Motor data for graphical estimation of volt-drop

           Motor rating  Efficiency    Power       kVA       I s /I n  Power    kVA at    Z ms at
           (kW)           (per-unit)  factor at  rating at  ratio   factor at  starting  starting
                                      full load  full load          starting             per-unit
                315        0.9455     0.8603      387.2    6.787     0.217     2628.3    0.1473
                430        0.9537     0.8715      517.4    6.445     0.219     3334.3    0.1552
                630        0.9595     0.8780      747.8    5.838     0.208     4365.6    0.1713
                720        0.9608     0.8788      852.6    5.619     0.202     4790.9    0.1780
                800        0.9617     0.8791      946.3    5.453     0.196     5158.6    0.1834
              1,100        0.9638     0.8780     1299.8    5.000     0.179     6498.5    0.2000
              1,500        0.9654     0.8756     1774.4    4.661     0.162     8270.0    0.2145
              2,500        0.9680     0.8722     2961.0    4.347     0.137    12,872     0.2300
              5,000        0.9717     0.8742     5886.6    4.397     0.111    25,883     0.2274
              6,300        0.9726     0.8763     7392.3    4.527     0.104    33,461     0.2209
              8,000        0.9730     0.8786     9358.1    4.712     0.096    44,093     0.2122
             11,000        0.9727     0.8806    12,843     5.017     0.086    64,440     0.1993


































           Figure G.4  Volt-drop when starting an induction motor. Volt-drop in per-unit versus the ratio of the motor
           kVA rating to the generation kVA capacity, for different values of generator per transient impedance Z g and
           standing load.

                    Figure G.4 shows the results of all the cases given in Table G.1. The volt-drop | V | is
              plotted against the ratio S motor /S gen so that a generalised presentation may be used. Note that
               these graphs can be used for most cases where generators up to about 30 MVA are present.
               Extrapolations can be used with confidence for generators above 30 MVA which have transient
   583   584   585   586   587   588   589   590   591   592   593