582    HANDBOOK OF ELECTRICAL ENGINEERING
































              Figure G.5  Volt-drop when starting an induction motor. Nomograph for the volt-drop in per-unit versus the
              ratio of the motor kVA rating to the generation kVA capacity, for a generator transient impedance Z g of 0.2 pu
              and zero standing load. The motor can have different ratios of starting current to running current.
































              Figure G.6  Volt-drop when starting an induction motor. Nomograph for the volt-drop in per-unit versus the
              ratio of the motor kVA rating to the generation kVA capacity, for a generator transient impedance Z g of 0.3 pu
              and zero standing load. The motor can have different ratios of starting current to running current.