Page 590 - Handbook of Electrical Engineering
P. 590

CALCULATION OF VOLT-DROP IN A CIRCUIT CONTAINING AN INDUCTION MOTOR      583

































           Figure G.7  Volt-drop when starting an induction motor. Nomograph for the volt-drop in per-unit versus the
           ratio of the motor kVA rating to the generation kVA capacity, for a generator transient impedance Z g of 0.2 pu
           and 0.8 pu standing load. The motor can have different ratios of starting current to running current.
































           Figure G.8  Volt-drop when starting an induction. Nomograph for the volt-drop in per-unit versus the ratio of
           the motor kVA rating to the generation kVA capacity, for a generator transient impedance Z g of 0.3 pu and
           0.8 pu standing load. The motor can have different ratios of starting current to running current.