Page 594 - Handbook of Electrical Engineering
P. 594

EARTHING CURRENT AND ELECTRIC SHOCK HAZARD POTENTIAL DIFFERENCE       587

                            Table H.1a. Earth fault current as a function of earth resistance

                            Earth        Earth      Proportion of current  X-to-R
                            resistance    fault       diverted to the    ratio
                            (ohms)       current                          (pu)
                                         (amps)    O/H line    Pole
                                                     (pu)       (pu)
                               0.25     1314.73     0.0683     0.9692    1.6023
                               0.50     1310.23     0.0777     0.9647    1.5876
                               0.75     1305.70     0.0870     0.9601    1.5736
                               1.00     1301.13     0.0962     0.9555    1.5602
                               1.25     1296.54     0.1053     0.9509    1.5474
                               1.50     1201.92     0.1143     0.9463    1.5351
                               1.75     1287.30     0.1233     0.9416    1.5233
                               2.00     1282.66     0.1321     0.9370    1.5121
                               4.00     1245.83     0.1992     0.8993    1.4383
                               6.00     1210.65     0.2603     0.8617    1.3874
                               8.00     1178.15     0.3156     0.8248    1.3532
                              10.0      1148.73     0.3654     0.7890    1.3311
                              15.0      1088.41     0.4695     0.7065    1.3094
                              20.0      1043.88     0.5496     0.6347    1.3141
                              25.0      1010.86     0.6120     0.5734    1.3307
                              30.0       985.98     0.6611     0.5211    1.3523
                              35.0       966.84     0.7005     0.4754    1.3754
                              40.0       951.83     0.7325     0.4382    1.3985
                              50.0       930.11     0.7808     0.3765    1.4417
                              60.0       915.38     0.8153     0.3292    1.4794
                              70.0       904.88     0.8409     0.2920    1.5120
                              80.0       897.07     0.8605     0.2622    1.5399
                              90.0       891.08     0.8760     0.2377    1.5640
                             100.0       886.36     0.8885     0.2173    1.5850
                            Note 1. These are in relation to the magnitude of the total current, since
                            both currents are complex quantities having different phase angles.

                 Table H.1a shows the value of I f for different values of R ep . It also shows the division of
           current between the overhead line earthing conductor and the footings of the pole.

                 Table H.1b shows the ‘doubling factor’, the peak factor and the power factor of currents that
           flow in an inductive circuit that has different X-to-R or R-to-X factors.
                 A small site may be constrained by a number of factors. Assume the site is located in a region
           of high resistivity with a low water table. The constraints on the design are:-

           • The surface resistivity is higher than that of the lower soil.
           • A grid with earthing rods attached will be needed.
           • Use a rod diameter no less than 0.01 m.
           • Allow the rods to be driven deep into the ground.
                                                        2
           • Use the least site area as possible, i.e. 30 to 256 m .
           • Let the overhead earthing conductor divert some of the fault current.
   589   590   591   592   593   594   595   596   597   598   599