Page 71 - Handbook of Electrical Engineering
P. 71

50    HANDBOOK OF ELECTRICAL ENGINEERING

              Similarly for generators Nos. 2 and 3,

                                        f z2 = 61.411 Hz and f z3 = 61.951 Hz

              Step 7.  Find the new set points that will recover the frequency to 60 Hz whilst maintaining equally
              loaded generators.
                    Let the desired frequency of 60 Hz be denoted at f d . In order to reach this frequency all the
              set points need to be increased by the difference between f d and f ,which is,

                                      f = f d − f = 60.0 − 59.25101 = 0.749 Hz

              Therefore,

                                          f z1 = 60.871 + 0.749 = 61.62 Hz
                                          f z2 = 61.411 + 0.749 = 62.16 Hz

              and
                                          f z3 = 61.951 + 0.749 = 62.70 Hz

              Check that f has now the correct value, by using (2.62),

                                             D 1 P 1 f o      0.03 × 18.0 × 60
                                    f = f z1 −      = 61.62 −
                                               G 1                  20
                                      = 61.62 − 1.62 = 60.0Hz
                                                              0.04 × 13.5 × 60
                                             D 2 P 2 f o
                                    f = f z2 −      = 62.16 −
                                               G 2                  15
                                      = 62.16 − 2.16 = 60.0Hz
              and,
                                             D 3 P 3 f o      0.05 × 9.0 × 60
                                    f = f z3 −      = 62.70 −
                                               G 3                  10
                                      = 62.70 − 2.70 = 60.0Hz


              2.5.5 Load Sharing Controllers

              The above worked example illustrates the combination of droop governing with an overall isochronous
              control function. In a practical control scheme the following variables can be easily measured by
              suitable transducers,

               f = the system frequency.
               P i = the electrical power at the terminals of the generator (the generator losses and
                    gearbox losses can be ignored).
              f zi = the governor set point within the controller that drives the fuel valve. A suitable
                    potentiometer can be used to derive the signal.
   66   67   68   69   70   71   72   73   74   75   76