Page 68 - Handbook of Electrical Engineering
P. 68

GAS TURBINE DRIVEN GENERATORS      47

                     setting must be reduced from 102.4% (61.44 Hz) to 101.6% (60.96 Hz) i.e. the same as
                     that of Gen.2. The common new frequency will be at point ‘D’ as 99.6% (59.76 Hz).
           Method 2. Change the speed setting of Gen.2 only:
                     The droop characteristic line 2A-A must be raised to the new position 2B-B so that it
                     crosses the line 1A-B of Gen.1 at point ‘B’ for 50% sharing of load. Thus the speed
                     setting must be raised from 101.6% (60.96 Hz) to 102.4% (61.44 Hz) i.e. the same as
                     that of Gen.1. The new frequency will be at point ‘B’ as 100.4% (60.24 Hz).
           Method 3. Change the speed setting of Gen.1 and Gen.2.
                     In order to recover the frequency to 100% (60 Hz) both speed settings will need to
                     be changed.
                     Gen.1 speed setting will be reduced to 102% (61.2 Hz).
                     Gen.2 speed setting will be raised to 102%.
                     The operating point will be ‘C’.
                     The droop lines will be 1C-C and 2C-C.


           2.5.4.1 Worked example
           Three generators have different ratings and operate in a power system that has a nominal frequency
           of 60 Hz. Each generator is partially loaded and the total load is 25 MW.
           a) Find the loading of each generator and the system frequency if the total load increases to 40.5 MW,
              whilst their set points remain unchanged.
           b) Also find the changes required for the set points that will cause the system frequency to be restored
              to 60 Hz. The initial loads on each generator and their droop values are, shown in Table 2.6.
           c) Find the changes in the set points that will enable the generators to be equally loaded at the new
              total load, with the system frequency found in a).
           d) Find the additional changes in the set points that will enable the frequency to be recovered to
              60 Hz.

           Step 1. Find the initial set points f zi before the load is increased. Transpose (2.62) to find f zi

                                                       D i P i f o
                                             f zi = f +                                   (2.69)
                                                        G i
           For generator No. 1,
                                              0.03 × 60.0 × 10.0
                                  f z1 = 60.0 +                = 60.9Hz
                                                     20
                               Table 2.6.  Data and initial conditions of three generators

                              Generator rating  Initial loading  Drop in per unit
                                 (MW)              (MW)
                                   20               10               0.03
                                   15               10               0.04
                                   10                5               0.05
   63   64   65   66   67   68   69   70   71   72   73