Page 93 - Handbook of Electrical Engineering
P. 93

SYNCHRONOUS GENERATORS AND MOTORS        73

                                      Table 3.1.  Preferred rated voltages of
                                      generators
                                      Generator     Approximate voltage
                                      rating (kVA)     rating (volts)

                                                     Min.      Max.
                                          100         200       450
                                          200         200       800
                                          500         300      3,000
                                         1,000        400      7,500
                                         2,000        600     15,000
                                         5,000       2,000    15,000
                                        10,000       5,000    15,000
                                        20,000      10,000    15,000
                                        30,000      15,000    15,000


           present. This can only be achieved by under-exciting the generator, thereby causing it to operate near
           or in its leading power factor region.

                 The above situation cannot normally occur with a self-contained power plant such as those on
           marine installations, unless they are interconnected by submarine cables to other installations that also
           have running generators. Even with interconnections of typically 20 km the amount of capacitance
           charging current is not sufficient to cause generators to operate in their leading power factor regions.
           It is possible under abnormal operating conditions, but these are too rare to consider. Oil industry
           power plants operate with a lagging power factor at or near to 0.9.
                 In conclusion it can be seen that the use and benefit of power-angle charts are minimal for
           most oil industry power plants.


           3.7 CHOICE OF VOLTAGES FOR GENERATORS

           The rated voltage of generators tends to increase in steps as the power rating increases. The most
           preferred voltages are given as a guide in Table 3.1. See also IEC60038.


           3.8 TYPICAL PARAMETERS OF GENERATORS

           Often at the beginning of a design project it is necessary to carry out some basic calculations and
           studies. For example, estimating the maximum fault current at the main generator switchboard and
           a preliminary stability assessment. At this stage equipment will not have been fully specified and
           so definitive data are not available from the chosen manufacturers. Typical data need to be used.
           Figures 3.5 through 3.12 show typical reactances and time constants for generators in the range 1.0
           to 40 MVA drawn from a modest sample of generators. In each figure it can be seen that there
           is a spread of points about the average line. This is partly due to the data being taken from some
           generators that have had constraints placed on them for minimum fault currents and volt drops. Other
           generators were closer to the standard or preferred design of the manufacturer. For preliminary studies
           and calculations the data taken from the average (or trend) lines would give reasonable results. If
           worst-case situations are to be considered then a value either side of the trend line within the range
   88   89   90   91   92   93   94   95   96   97   98