Page 176 - Handbook of Energy Engineering Calculations
P. 176

value of K  and solving for T , the evaporator exit-gas temperature, ln[(880
                                                   g2
                            1
               − 366)/(T  − 366)] = 387.6(165,000)           –0.4  ; T  = 388 °F (197.8°C). Then, the
                           g2
                                                                     g2
               evaporator duty, using the same equation as in step 1 above = (165,000)(0.99)
               (0.27)(880 − 388) = 21.7 MM Btu/h (6.36 MW).
                  In  this  calculation,  we  assumed  that  the  exhaust-gas  analysis  had  not

               changed.  If  there  are  changes  in  the  exhaust-gas  analysis,  then  the  gas
               properties  must  be  evaluated  and  corrections  made  for  variations  in  the
               exhaust-gas temperature. See Waste Heat Boiler Deskbook by V. Ganapathy
               for ways to do this.



               5. Find the assumed duty, Q , for the economizer
                                                  a
               Let  the  economizer  leaving-water  temperature  =  360°F  (182.2°C).  The
               enthalpy  of  the  feedwater  =  332  Btu/lb  (773.6  kJ/kg);  saturated-steam

               enthalpy = 1195.7 Btu/lb (2785.9 kJ/kg); saturated-liquid enthalpy = 338.5
                                                                                                6
               Btu/lb (788.7 kJ/kg). Then, the steam flow, as before, = (21.5 × 10 )/[(1195.7
               −  332)  +  0.05  (338.5  –  332)]  =  25,115.7  lb/h  (11,043  kg/h).  Then,  the

               assumed duty for the economizer, Q  = (25,115.7)(1.05)(332 − 198.5) = 3.52
                                                           a
               MM Btu/h (1.03 MW).


               6.  Determine  the  UA  value  for  the  economizer  in  both  design  and  off-

                  design conditions
               For the design conditions, UA = Q/(ΔT), where Q = economizer duty from
               step 2, above;Δ T = design temperature conditions from the earlier data in this
                                                                      6
               procedure.  Solving,  UA  =  (3.84  ×  10 )/{[(299  −  230)  −  (408  −
               373)]/ln(69/35)} = 76,800 Btu/h°F (40.5 kW). For off-design conditions, UA
               =  (UA  at  design  conditions)  (gas  flow  at  off-design/gas  flow  at  design

               conditions)   0.65  = (76,800) (165,000/140,000)      0.65  = 85,456 Btu/h°F (45.1 kW).


               7. Calculate the economizer duty
               The energy transferred = Q  = (UA)(Δ T). Based on 360°F (182.2°C) water
                                                 t
               leaving the economizer, Q  = 3.52 MM Btu/h (1.03 MW). Solving for t  as
                                               a
                                                                                                       g2
                                                   6
               before  =  382  −  [(3.52  ×  10 )/(165,000)(0.9)(0.253)]  =  388  −  85  =  303°F
               (150.6°C).  Then,ΔT  =  [(303  −  230)  −  (388  −  360)]/ln(73/28)  =  47°F
               (26.1°C).  The  energy  transferred  =  Q   =  (UA)(Δ T)  =  (85,456)(47)  =  4.01
                                                              t
   171   172   173   174   175   176   177   178   179   180   181