Page 560 - Industrial Power Engineering and Applications Handbook
P. 560
16/534 Industrial Power Engineering and Applications Handbook
1. Conductor
2. Conductor screening
3. Impregnated-paper
insulation
4. Screening (metallized
paper)
5. Tape
6. Belt insulation
7. Lead sheath
8. Bedding
9. Armouring
IO. Outer serving
Belted construction in which Screen construction (H type) in Screened SL construction (HSL
insulation in the form of which each core has its own type) which, in addition to
common belt, in addition to insulation and screen possessing its own insulation
core insulation, is employed and screen also has a separate
lead sheath for each core as
against a common lead sheath
in the other two types
Figure A16.1 Different constructions of paper-insulated cables
Extruded
7 semi-conducting conductor shielding
Aluminium conductor
TROPOTHEN-X insulation
I
semi-conducting
shielding
Extruded
core
TROPODUR outer sheath
Copper tape screening
Core identification tape
Figure A16.2 Three-core XLPE cable (Courtesy: CCI)