Page 594 - Industrial Power Engineering and Applications Handbook
P. 594

Voltage surges-causes,  effects and remedies  171559
      are of  a momentary  nature. Field studies have revealed   negative, which creates a voltage gradient between the
      that such causes contribute nearly 90% of the total tripping.   clouds or between the clouds and the each. The voltage
      During  such  faults,  the  interrupters  at  both  ends  of  a   gradient may exceed the breakdown value of the air and
      transmission line may trip as a result of travelling surges   cause  a  flashover.  This  flashover  is  similar  to  an
      in both directions. An auto-reclosing scheme, which may   electrostatic discharge of the atmosphere to the ground,
      be  applied  to  an  overhead  transmission  or a long  HT   as illustrated  in Figure  17.1, and is termed  a lightning
      distribution system, can reclose the interrupter on such a   strike. There may be up to 20 pulses  in each lightning
      trip in about 10-15  cycles and maintain the supply system   strike,  each  having  a  duration  of  about  50 ps. The
      intact, preventing loss of synchronism. Thus it helps to   phenomenon is comparable to the discharge of a highly
      achieve a high degree of system stability.     charged condenser, the clouds forming one plate, ground
        Since the fault is of  a transitory  nature,  the  scheme   the other and the air as the dielectric.
      may be applied even on a per-pole basis,  allowing the
      healthy  phases  to  remain  intact  and  the  reclosing   Electrostatically induced charges
      necessitated only in the affected phase rather than all the
      phases,  thus  further  enhancing  the  system’s  transient   Due to the presence of thunder clouds in the vicinity:
      stability.  However,  it  would  require  an  independent   A charged cloud above and near a large object, an
      interrupting  mechanism  and  individual  relaying  and   overhead  line  for  instance,  induces  a  charge  of
      tripping schemes for each pole.                   opposite polarity than its own in the line. When this
        It  is possible  that  the  breaker  may  trip  on the  first   cloud  bursts  suddenly  and  discharges,  its induced
      reclosing after a fault, as the fault may not have cleared.   electrostatic charge travels in both directions of the
      In such cases a delayed reclosing,  with a delay  of  one   line, with a near velocity of light and equalizes the
      second or so, may  also be incorporated  into the  same   potential  at  all  points.  The potential  at  any  point
      switching  scheme to  supplement  the  fast reclosing,  to   along the line rises suddenly from its normal value
      save the system from a saving and a consequent trip. By   to the amplitude (V,) of the travelling wave.
      then the fault would clear in all probability to allow the   Due to  the  friction  of  dust  or free  snow  blowing
      breaker to reclose thus maintaining the continuity of supply   past the conductors.
      once again  and  saving the  system from  falling  out  of
      synchronism and a tandem trip of all the feeding lines of   Electromagnetically induced currents
      a power grid. If  the fault persists  and the breaker  trips
      again, the breaker will lock out and will not close again   Due to lightning in the vicinity of the overhead lines. It
      until the fault is removed and the breaker is reset.   is an indirect  effect of  a lightning strike. The lightning
        Delayed reclosing  may be adopted where the system   surges may impose very severe stresses on the line and
      has large interconnections  (mesh system) as at a power   cause  damage  to  the  line  insulators  and  the  terminal
      grid, and where loss of one phase may not cause a loss   equipment without causing a trip by the protective device.
      of synchronization in such a duration and hence restore   These surges can be contained at the receiving end with
      the transient stability of the whole system.   the use of a surge arrester or a diverter (discussed later).

                                                     17.5.2  Internal causes
      17.5  Causes of voltage surges
                                                     Making or breaking  a power circuit causes a change in
      In  actual  operation,  disturbances  on  a  power  system,
      causing  sudden changes in the  system parameters,  are
      quite frequent and may generate temporary overvoltages
      and voltage  surges,  as summarized  above. The system
      disturbances  may be of two types, external or internal,
      as explained below.

      17.5.1  External causes
      These  are  mainly  due  to  atmospheric  disturbances  as
      noted below. The effect of such surges is totally different
      from  that  of  switching  surges,  and  the  amplitude  is
      independent of the system voltage.
      Lightning strike

      There is no clear explanation of lightning. However, the
      most  popular  theory  is the  charging  of  clouds at high
      voltages, up to 20 million volts and a charging current
      5-100  kA or so, due to the movement of hot air upwards
      and big droplets of water downwards. This process tends
      to make the tops of  the clouds positive  and the bottom   Figure 17.1  Discharge from clouds
   589   590   591   592   593   594   595   596   597   598   599