Page 969 - Industrial Power Engineering and Applications Handbook
P. 969

Parameter.5                                  Standard copper   Commercial purity aluminium (for electricul use)
                                                           (IACS)a
                                                                                                       ~~    ~
              Volume conductivity      m/Gmm2              58                34.80                  32.26127.8         3 1.90
              Conductivity             % IACS*             100              61/60                   50148              55
              Temperature coefficient  of electrical resistance
              per "Cu.20  (applicable over a working  range of   3.93 x  10-1   4.03 X  10-'/3.96  X  lo-'   3.3 x  10-'/3.168  x   3.63 x  IO-'
              100-200°c)
              a10 at a particular conductivity
              =   at 100% conductivity x actual conductivity
              of the metal.
                                                        ~-                ~       - ~~
              Coefficient of linear expansion (thermal), (md'C)   1.73 x    2.3 x                   2.3   10-5         2.3 x
              (applicable over a working  range of 20-200°C)
              Mass resistivity = volume resistivity x density (~X2.gm/crn2)   15.328   7.786        83719.72           8.49
              Notes
              When using the above metals for the purpose of current carrying, their mechanical suitability must be checked with the data provided above to withstand, without permanent deformation, the
              electrodynamic forces that may develop during  a short-circuit condition (Section 28.4.2).
              For important definitions, refer to Section 30.1.1.
              These values are based  on the mean values of  a number of  tests carried out on specimens of  standard copper and aluminium  conductors.
              a  IACS - International  Annealed Copper Standard
               Suffix M (now F) or WP (now T6) represent the type of tempering.
               EIE, HE9 and E91E are old designations. They have now  been replaced by  1350, 6063 A and 6101 A respectively.