Page 476 - Industrial Wastewater Treatment, Recycling and Reuse
P. 476
446 Industrial Wastewater Treatment, Recycling, and Reuse
and communication. The technology provides access to comprehensive, real-
time data, alarms, and reports that help to speed resolution of issues and pro-
mote collaboration on continuous improvement and value creation. This
component is instrumental in creating, capturing, and delivering value to
the users of the technology.
11.2.5 Case Study
3D TRASAR Technology for Sugar equipment was installed at a large raw
sugar mill. The mill faces water scarcity and consequently reuses process
condensate in its low-pressure boilers. For monitoring the process conden-
sate quality, an a-naphthol test was done every 15 minutes. In Figure 11.7,
the performance of the conductivity sensor is shown. The crosses represent
the a-naphthol data points from the operator logs. The results from the test
are qualitative and are logged as nil, trace, very faint, and so forth, depend-
ing upon the color intensity of the ring that develops for the sample under
test. The a-naphthol test data indicates that there is an entrainment event
Figure 11.7 Comparison of sugar fluorometer data, conductivity, and the Molisch test.
Conductivity shows a poor correlation with sugar concentration.