Page 145 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 145
Q S 2 sin 2 1 cos PF 80 kW sin cos 1 0.8 48 kvar
The real, reactive, and apparent power supplied to the plant is
P TOT P 1 P 2 100 kW 64 kW 164 kW
Q TOT Q 1 Q 2 48.4 kvar 48 kvar 96.4 kvar
S TOT P TOT 2 TOT 2 Q 164 kW 2 96.4 kVA 2 190 kVA
The line current is given by
S 190 kVA
I TOT 228.5 A
L
3 L V V 3 480
Note: In the following sections, we will treat the synchronous motor as though it
were Y connected. The problem doesn’t specify the connection, and the
answers are the same whether we assume a or a Y connection, so we will
just choose one for convenience.
(b) The rated power of the motor is P motor 100 hp 746 W/hp 74.6 kW . Assuming that the
motor is Y-connected, the base quantities for the synchronous motor are
S P / PF 74.6 kW / 0.8 93.2 kVA
base
V 460 V
L ,base
V ,base V L,base / 3 460 V / 3 266 V
S 93.2 kVA
I base 117 A
L ,base
3V L ,base V 3 460
I ,base I L ,base 117 A
3 V 2 3 266 V 2
Z ,base 2.278
,base
S base 93,200 VA
Therefore the impedances can be expressed in ohms per phase as
R A Z ,base R A ,pu 2.278 0.01 0.023
X S Z ,base S ,pu X 2.278 2.51 1.1
The rated real and reactive power of the motor is
P 100 hp 746 W/hp 74.6 kW
motor
Q motor P tan motor 1 cos PF 74.6 kW tan cos 1 0.8 56 kvar
Note that the motor is supplying reactive power, not consuming it.
The phase voltage would be V V L / 3 480 V / 3 277 V , and magnitude of the armature
current would be
139