Page 146 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 146
P 74.6 kW
I motor 112 A
A
3V cos 3 277 V 0.8
Since the power factor is 0.8 leading, the current Ι A 112 36.87 A , and the internal generated voltage
is
E V R I jX I
A A A S A
E 277 0 V 0.023 112 36.87 A j 2.51 112 36.87 A
A
E 498 27.0 pu
A
The field current must corresponding to 498 V is 1.86 A.
(c) The torque angle of the motor is 27
(d) The real, reactive, and apparent power supplied to the plant is
P TOT P 1 P 2 P motor 100 kW 64 kW+74.6 kW 238.6 kW
Q TOT Q 1 Q 2 Q motor 48.4 kvar 48 kvar 56 kvar 40.4 kvar
S TOT P TOT 2 TOT 2 Q 238.6 kW 2 40.4 kVA 2 242 kVA
The line current is given by
S 242 kVA
I L TOT 291 A
3 L V 3 480 V
(e) If the field current is increased to 2 A, the magnitude of the internal generated voltage will rise from
498 V to 517 V (see the OCC curve). The power supplied to the load will remain constant (because the
load torque and rotational speed are unchanged), so the distance E A sin P will remain constant.
Therefore the torque angle becomes
E 1 498 V
sin 1 A 1 sin 1 sin sin 27 25.9
2
E A 2 517 V
The new armature current is
V E 277 0 V 517 25.9 V
I A 2 117 39.8 A
A
2
jX S j 2.51
The current angle is 39.8, so the impedance angle 39.8 . The real power supplied by the motor is
P motor 3V I cos 3 277 V 117 A cos 39.8 74.6 kW
Q motor 3V I cos 3 277 V 117 A sin 39.8 62.2 kvar
(f) The torque angle of the motor is 39.8
(g) The power factor of the motor is cos 39.8 0.768 leading .
(h) The real, reactive, and apparent power supplied to the plant is
P TOT P 1 P 2 P motor 100 kW 64 kW+74.6 kW 238.6 kW
140