The rated current of this generated is 50 A, so 40 A is 80% of full load. If the full load armature reaction
is 300 Aturns, and if the armature reaction is assumed to change linearly with armature current, then the
armature reaction will be 240 Aturns. The demagnetizing effect of armature reaction is equivalent to a
reduction in field current of
240 A t
I 0.24 A
F
1000 t
The figure below shows that a triangle consisting of 7.2 V and (240 Aturns)/(1000 turns) = 0.24 A fits
exactly between the E A and V T lines at a terminal voltage of 105 V.