The rated current of this generated is 50 A, so 40 A is 80% of full load.  If the full load armature reaction
                 is 300 Aturns, and if the armature reaction is assumed to change linearly with armature current, then the
                 armature reaction will be 240 Aturns.  The demagnetizing effect of armature reaction is equivalent to a
                 reduction in field current of

                                    
                               240 A t
                          I           0.24 A
                           F
                               1000 t
                 The figure below shows that a triangle consisting of 7.2 V and (240 Aturns)/(1000 turns) = 0.24 A fits
                 exactly between the  E A  and V T   lines at a terminal voltage of 105 V.