Page 261 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 261

(c)  The rated current of this generator is 50 A, so 20 A is 40% of full load.  If the full load armature
                 reaction is 300 Aturns, and if the armature reaction is assumed to change linearly with armature current,
                 then the armature reaction will  be  120  Aturns.  The demagnetizing effect of armature reaction is
                 equivalent to a reduction in field current of

                                    
                              120 A t
                          I           0.12 A
                           F
                               1000 t
                 The figure below shows that a triangle consisting of 3.6 V and (120 Aturns)/(1000 turns) = 0.12 A fits
                 exactly between the  E A  and V T   lines at a terminal voltage of 114 V.

































                                                           255
   256   257   258   259   260   261   262   263   264   265   266