Page 296 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 296
SOLUTION Since the transmission lines are lossless in this power system, the full voltage generated by G
1
will be present at each of the loads.
(a) Since this load is Y-connected, the phase voltage is
480 V
V 277 V
1
3
The phase current can be derived from the equation P 3V I cos as follows:
P 100 kW
I 1 3 cos 3 277 V 0.9 133.7 A
V
(b) Since this load is -connected, the phase voltage is
V 480 V
2
The phase current can be derived from the equation S 3V I as follows:
S 80 kVA
I 2 55.56 A
3V 3 480 V
(c) The real and reactive power supplied by the generator when the switch is open is just the sum of the
real and reactive powers of Loads 1 and 2.
P 100 kW
1
Q 1 P tan P tan 1 cos PF 100 kW tan25.84 48.4 kvar
P 2 S cos 80 kVA 0.8 64 kW
Q 2 S sin 80 kVA 0.6 48 kvar
P G P 1 P 2 100 kW 64 kW 164 kW
Q G Q 1 Q 2 48.4 kvar 48 kvar 96.4 kvar
P Q
(d) The line current when the switch is open is given by I , where tan 1 G .
L
3 V L cos P G
tan 1 Q G tan 1 96.4 kvar 30.45
P G 164 kW
P 164 kW
I 228.8 A
L
3 V L cos 3 480 V cos 30.45
290