Page 96 - Low Temperature Energy Systems with Applications of Renewable Energy
P. 96

Characteristics of low-temperature energy sources for heat pumps   85

              The required compressor power is

               Q 0 ¼ 20:0   4:9 ¼ 15:1kW

              The length of the collector pipes is


                  15100 3:5   1
               L ¼               ¼ 568 m
                   19:0    3:5
              For the construction of a ground collector, three 190 m long loops are
           required.
              The required area of the site to accommodate the collector is

                       n   1
               A ¼ L   a
                         n
                            3   1       2
               A ¼ 568   0:75    ¼ 284 m
                              3

              Vertical collector
              The specific heat flow from the soil to the pipes of the vertical collector is

               q 0 ¼ 1:2½ð1:4   1:61Þ  0:5Šð0:4 þ 1Þð8   0Þ¼ 23:5W=m

              The length of vertical manifold pipes is


                  15100 3:5   1
               L ¼               ¼ 459 m
                   23:5    3:5
              We accept the collector design of five wells, each with a depth of 92 m.



           Exercises

           1. Determine the length of a horizontal ground heat exchanger for a heat pump with a capacity
              of: A: 25 kW; B: 10 kW. The heat exchanger is laid in soil consisting of clay with a moisture
              content of 10%; the soil temperature at a depth of 2 m is 5 C.

           2. Determine the length of the vertical ground heat exchanger for a heat pump: A: 250 kW; B:
              100 kW. Geological data: at a depth of up to 100 m, the soils are represented by sand with a
              moisture content of 5%; soil temperature is 10 C.

           3. Determine the coefficient of performance of a heat pump system with a ground heat
              exchanger. The heating system is radiant floor heating. R410a (Case A) and R407a (Case
              B) are used as heat pump working fluids.