Page 190 - Mechanical Engineers' Handbook (Volume 2)
P. 190

9 Flow Rate   179
                                                       1.38   P
                                                   calib       calib
                                                            R AIR calib
                                                                T
                                                            (25   14.7)(144)
                                                       1.38                  0.279
                                                           (53.3)(460   70 F)
                                                W calib    (1.44)(1.38)(.075)   0.149 lb /s
                                                                              m
                                                               0.585
                                                 W     (0.149)        0.216 lb /s
                                                  USE                        m
                                                             	 0.279
                                                        W       W
                                            SCFM (USE)     USE     USE    2.877 SCFM
                                                                0.075
                                                        STD,AIR
                              This correction equation was derived under the assumption that the float was held up
                           only by the pressure force (i.e., buoyancy and viscous drag were both negligible). When
                           metering liquids of high density, the buoyant force must be accounted for, and if the viscosity
                           of the fluid exceeds the viscosity immunity ceiling for a given meter, then the viscous drag
                           must be taken into account. Precautions for dealing with these two cases are covered by the
                           manufacturer’s instructions. A meter purchased for gas service cannot be converted to liquid
                           service by the preceding equation, or vice versa; a new calibration is required.
                              Variable-area meters are generally limited in accuracy to  1or  2% of full-scale
                           reading.
                              It is important to measure the actual density of the fluid flowing in the meter to ensure
                           that the calibration conditions are properly met. Pressure and temperature must be measured
                           at the meter, just upstream of the float.
                              Irreversibilities involved in the mixing of the annular jet introduce losses in pressure
                           that are nearly independent of flow rate and roughly equal to the pressure required to hold
                           up the float. More accurate meters generally have higher losses (up to 3 or 4 psi used with
                           air).


            9.5  Laminar Flowmeters

                           Commercial laminar flowmeters consist of a matrix or core of small-diameter passages ar-
                           ranged so that the pressure drop across this core can be measured. The meter must be sized
                           properly so the flow in these passages will remain laminar, even at the highest rated flow.
                           If the flow remains laminar, then the pressure drop is linearly related to the volume flow
                           rate through the core. General commercial practice is to provide flow-straightening sections
                           upstream and downstream of the core and measure the pressures in the space between the
                           flow straighteners and the core, as shown in Fig. 28.
                              Laminar flowmeters produce a pressure difference, usually 0–8 in. H O, which must be
                                                                                    2
                           measured using an appropriate auxiliary instrument. The meter responds to volume flow;
                           hence it is also necessary to measure the density of the fluid flowing. If the composition is
                           known, density can be calculated knowing temperature and pressure at the inlet.
                              The pressure drop across a well-designed laminar flowmeter is linearly proportional to
                           the volume flow rate (ACFM) multiplied by the viscosity of the fluid flowing. The pressure
                           drop is independent of density.
                              Each meter is accompanied by a calibration curve, which typically reads:
                              Air Flow in Cubic Feet per Minute at 70 F and 29.92 Inches of Mercury Absolute vs.
                                Pressure Drop, Inches of Water.
   185   186   187   188   189   190   191   192   193   194   195