Page 463 - Mechanical Engineers' Handbook (Volume 4)
P. 463

452   Refrigeration

                                . These are extremely corrosive to many exchanger materials, yet difficult to detect
                          and CO 2
                          in sampling. Pump power, water treatment, and special condenser material should be eval-
                          uated when considering costs.
                             Allowances must be made in heat-transfer calculations for fouling or scaling of ex-
                          changer surfaces during operation. This ensures sufficient surface to maintain rated perform-
                          ance over a reasonable interval of time between cleanings. Scale-factor allowances are
                                     2
                          expressed in m  K/kW as additional thermal resistance.
                                                                                           2
                             Commercial practice normally includes a scale-factor allowance of 0.088 m  K/kW.
                          The long hours of operation usually associated with chemical-plant service and the type of
                          cooling water frequently encountered generally justify a greater allowance to minimize the
                          frequency of downtime for cleaning. Depending on these conditions, an allowance of 0.18
                                  2
                          or 0.35 m  K/kW is recommended for chemical-plant service. Scale allowance can be re-
                          flected in system designs in two ways: as more heat-exchanger surface or as higher design
                          condensing temperatures with attendant increase in compressor power. Generally, a compro-
                          mise between these two approaches is most economical. For extremely bad water, parallel
                          condensers, each with 60–100% capacity, may provide a more economical selection and
                          permit cleaning one exchanger while the system is operating.
                             Air-cooled condensing equipment can also be used in refrigeration systems. With tighter
                          restrictions on the use of water, air-cooled equipment is used even on larger centrifugal-type
                          refrigeration plants, although it requires more physical space than cooling towers. Larger
                          condensers include an array of propeller fans located at the top of the condenser that pull
                          air over the condensing coil. Circulating fans and exchanger surface are usually selected to
                          provide design condensing temperatures of 49–60 C when design ambient dry bulb temper-
                          atures range between 35 and 38 C.
                             The design dry bulb temperature should be carefully considered since most weather data
                          reflect an average or mean maximum temperature. If full load operation must be maintained
                          at all times, care should be taken to provide sufficient condenser capacity for the maximum
                          recorded temperature. This is particularly important when the compressor is centrifugal be-
                          cause of its flat head characteristics and the need for adequate speed. Multiple-circuit or
                          parallel air-cooled condensers must be provided with traps to prevent liquid backup into the
                          idle circuit at light load. Pressure drop through the condenser coil must also be considered
                          in establishing the compressor discharge pressure.
                             The condensing temperature and pressure must be controlled for the refrigeration system
                          to function optimally. Too high a condensing temperature results in increased power and
                          reduced capacity. Too low a condensing temperature can result in poor performance of the
                          expansion device. Air-cooled condensers often employ fan cycling, modulating dampers, or
                                                                                             18
                          fan speed control to maintain proper refrigerant condensing temperature and pressure. On
                          condensers with multiple fans, one or more of the fans can each be cycled on and off to
                          maintain refrigerant conditions. When modulating dampers are used, the airflow through the
                          condenser can be controlled from 0 to 100%. Variable-speed drives can also be used to
                          control fan speed and airflow through the condenser.
                             In comparing water-cooled and air-cooled condensers, the compression power at design
                          conditions is usually higher with air-cooled condensing, because of the larger temperature
                          differential required in air-cooled condensers. However, ambient air temperatures are con-
                          siderably below the design temperature most of the time, and operating costs frequently
                          compare favorably over a full year. In addition, air-cooled condensers usually require less
                          maintenance, although dirty or dusty atmospheres may affect performance.

           7.3  Evaporators
                          There are special requirements for evaporators in refrigeration service that are not always
                          present in other types of heat-exchanger design. These include problems of oil return, flash-
                          gas distribution, gas–liquid separation, and submergence effects.
   458   459   460   461   462   463   464   465   466   467   468