Page 319 - Offshore Electrical Engineering Manual
P. 319

306    CHAPTER 4  Hazardous Area Installation




                          Table 5.4.2  Gas Group Examples
                                                                      Temperature
                          Material  Flashpoint (°C)  Ignition Temperature (°C) Class  Gas Group

                          Ethylene  Gas          425                  T2          IIB
                          Hydrogen  Gas          560                  T1          IIC
                          Methane  Gas           538                  T1          IIA
                          Kerosene  38           210                  T3          IIA
                          Propane  −104          466                  T1          IIA




                         EXPLOSION-PROOF EQUIPMENT GROUPS

                         The maximum dimensions for flamepaths in Ex ‘d’ equipment (see later), obtained
                         from experiment, are used by the responsible standards authorities to subdivide flam-
                         mable gases and vapours into three groups, A, B and C. The flamepath dimension is
                         associated with the molecular size of the gas, the largest being in group A. Group C,
                         which contains only hydrogen, is the most onerous as it requires the smallest flame-
                         path cross-section and hence the finest machine tolerances.
                            Some examples of ignition temperatures and flashpoints are given in Table 5.4.2.



                         INCREASED SAFETY EX ‘E’ EQUIPMENT
                         This type of protection relies on the reduction or to make negligible the risk of an
                         explosion by careful design of the motor and its control gear in order to eliminate any
                         potential sparking which may come in contact with an air/gas flammable mixture, or
                         an excessive temperature anywhere within or on the surface of the machine. Design
                         criteria for this type of motor are given in BS 5501 and BS 5000.
                            This type of protection is not used in North American equipment, and the stan-
                         dards have therefore been written with European voltages only in mind, quoting a
                         maximum nominal system voltage of 11 kV. Strictly speaking, equipment made for
                         the North American standard voltage of 13.8 kV cannot comply with these stan-
                         dards. However, it is usual under these circumstances for such motors to be tested
                         and then issued with a certificate of inspection rather than a certificate of author-
                         ity. Acceptance of this method of protection must therefore be obtained from the
                         platform certifying body and underwriters before any decision to use such a motor
                         is made.
                            Ex ‘e’ motors offer increasing savings in weight and bulk as ratings increase.
                         Beyond the 315 frame size, the only economic alternative is the Ex ‘p’ type of protec-
                         tion, as Ex ‘d’ would be too heavy or the castings too difficult to manufacture.
                            The following criteria should be considered by the installer to ensure certification
                         is not invalidated and/or the risk of explosion increased.
   314   315   316   317   318   319   320   321   322   323   324