Intrinsic Safety – Ex ‘i’a and Ex ‘i’b (Refer to BS EN 60079-11:2012)  309




                  INTRINSIC SAFETY – EX ‘I’A AND EX ‘I’B (REFER TO BS EN
                  60079-11:2012)

                  Where circuits are required purely for the transmission of signals, data, logic or
                  instructions, the energy in the circuit can be limited to level below which ignition
                  of explosive vapours/gases cannot occur. However, the circuits must also be pro-
                  vided with barriers which will prevent any faults from allowing these limits to be
                  exceeded. The barriers can utilise zenor diode circuits to blow a fuse, or can convert
                  the galvanic signal to an optical signal using ‘opto-isolators’. The ignition curves for
                  a resistive circuit are given in Fig. 5.4.1.















































                  FIGURE 5.4.1
                  Ignition curves for a resistive circuit.