314    CHAPTER 4  Hazardous Area Installation




















































                         FIGURE 5.4.3
                         Typical IS loop calculation.



                         addition of simple apparatus will not affect the compatibility, except that the system
                         temperature might be derated.
                            The system will be categorised according to the least favourable components of
                         the barrier category and the apparatus category. For example, a barrier of (Ex ia) IIC
                         with a field device of Ex ia IIC T6 will categorise the system as Ex ia IIC T6. The
                         addition of a field device of Ex ia IIC T4 will change the system category to Ex ia
                         IIC T4.