312    CHAPTER 4  Hazardous Area Installation















































                         FIGURE 5.4.2, cont’d



                         ‘SIMPLE’ APPARATUS AND COMPONENTS

                         Simple electrical apparatus and components (e.g., thermocouples, photocells, junc-
                         tion boxes, switches, plugs and sockets, resistors, LEDs) may be used in intrinsically
                         safe systems without certification provided that they do not generate more than
                         1.2 V, 0.1 A, and 25 mW in the intrinsically safe system in the normal or fault
                         conditions of the system.
                            The ‘Simple’ apparatus should conform to all relevant requirements of the BS
                         EN 60079-11. Simple apparatus intended for use in Zone 0 requires specific protec-
                         tive measures. For such apparatus, EN 60079-26 and EN 1127-1 apply in addition to
                         EN 60079-0 and 60079-11. Special requirements, e.g., for electrostatic charging of
   320   321   322   323   324   325   326   327   328   329   330