Page 323 - Offshore Electrical Engineering Manual
P. 323

310    CHAPTER 4  Hazardous Area Installation




                          Table 5.4.3  Relationships Between Different Methods of Assessing Safety
                          Levels

                          Level of      Countable    ATEX                    Normal Zone of
                          Protection    Faults       Category     IEC EPL    Use
                          ia            2            1            0          0
                          ib            1            2            1          1
                          ic            0            3            2          2




                         LEVEL OF PROTECTION ‘IA’
                         Intrinsically safe circuits in electrical apparatus of category ‘ia’ must not be capable
                         of causing an ignition during normal operation when two faults occur. The different
                         levels of protection and their interrelationships are given in Table 5.4.3.

                           1.   in normal operation and with the application of those non-countable faults
                            which give the most onerous condition;
                           2.   in normal operation and with the application of one countable fault plus those
                            non-countable faults which give the most onerous condition;
                           3.   in normal operation and with the application of two countable faults plus those
                            non-countable faults which give the most onerous condition.




                         LEVEL OF PROTECTION ‘IB’
                         Intrinsically safe circuits in electrical apparatus of level of protection ‘ib’ shall not be
                         capable of causing ignition in each of the following circumstances:

                           1.   in normal operation and with the application of those non-countable faults
                            which give the most onerous condition;
                           2.   in normal operation and with the application of one countable fault plus the appli-
                            cation of those non-countable faults which give the most onerous condition.




                         LEVEL OF PROTECTION ‘IC’
                         Intrinsically safe circuits in electrical apparatus of level of protection ‘ic’ shall not
                         be capable of causing ignition in normal operation. Where distances are critical for
                         safety, they shall meet the requirements of IEC 60079-11.
                            (Note: A countable fault is a fault which occurs in parts of electrical appara-
                         tus conforming to the constructional requirements of IEC 60079-11). The manu-
                         facturer is required to issue a certificate of conformity as typically shown in
                         Fig. 5.4.2.