Page 45 - Offshore Electrical Engineering Manual
P. 45

32     CHAPTER 1  Insulation and Temperature Ratings of Equipment




                         DO NOT READJUST AVR DURING HEAT RUN

                         Portable thermometers are attached to the air intake and outlet; in the latter case it is
                         advisable to run generator for a short while and determine the hottest spot by hand before
                         attaching the thermometer. Air thermometers must be no more than 2 m from generator.
                            When thermal stability is reached, take final hot load readings and running tem-
                         peratures and then shut down as quickly as possible. No specific time for shutdown
                         and taking hot temperatures is given in marine specifications.
                            With digital thermometer check spot temperatures and record as follows:

                          Stator core           (usually accessible through the terminal box)
                          Stator coils          (end windings)
                          Rotor coils           (At hottest spot, usually near coil supports)
                          Exciter armature      (Windings)
                          Exciter field         (Windings)
                          Bearings              (D. E. and N. D. E. temperatures to be recorded)

                            Take hot resistances of stator and exciter field windings.
                            On large generators, take rotor winding resistances as soon as possible after gen-
                         erator has stopped.
                            As mentioned earlier in this chapter, temperature rise by resistance is given by the
                         following formula:
                                               t 2 = [R 2 /R 1 (t 1 + 235)] − 235
                         where R  is the resistance of the winding cold, R  the resistance of the winding hot,
                                                                2
                                1
                         t  the temperature of the winding cold (°C), and t  the temperature of the winding hot
                          1
                                                                2
                         (°C) (Fig. 2.1.1).
                         RATINGS FOR VARIABLE SPEED MOTORS
                         Where motors are being supplied from converters, phase-angle controlled thyristor
                         drives or similar systems where the machine is subjected to prolonged running at sig-
                         nificant load but reduced speeds, a larger de-rated machine may be required because
                         the cooling effects of shaft-driven fans and windage will be reduced. Alternatively,
                         an independently driven cooling fan will be required. Because of this, it is preferable
                         to purchase the drive and motor as a unit with the appropriate ATEX Declaration of
                         Conformity from the manufacturer.



                         THERMAL OVERLOADS AND MOTOR THERMAL PROTECTION

                         During starting, both in the winding of the rotor and in the winding of the stator,
                         currents may be present that are well above regular on-load currents. A fast trip
                         must be initiated when a fault occurs during startup, for example, in the event
   40   41   42   43   44   45   46   47   48   49   50