Page 53 - Offshore Electrical Engineering Manual
P. 53

40     CHAPTER 2  AC Synchronous Generators




                                0.8
                                r                  Field heating limit
                                0.7
                                                                           0.8 PF
                                0.6
                           Into the system  (overexcited)  0.5                   m  0.9 PF


                                0.4
                                                                                     0.95 PF

                                0.3                                                  Armature
                                                                                      heating
                                                                                       limit
                                0.2
                                                                           k
                           Per-unit megavars  Q  o 0.0  0.1  θ  0.2  0.3  0.4  0.5  0.6  0.7  0.8  0.9  p  1.0 PF
                                0.1
                             +
                                                                                     1.0
                             –
                                                    Per-unit megawatts P
                                                                                      Prime
                                0.1
                                                                                      mover
                                                                                      limit
                                0.2
                                                          100% excitation circle
                                0.3                                                   0.95 PF
                           From the system  (underexcited)  0.4  δ  Underexcitation limit  m’  0.90 PF

                                0.5

                               0.58
                                0.6 n

                         FIGURE 2.2.3
                         Alternating current generator capability diagram. PF, power factor.




                            If the frequencies of the power supplied by the two generators are not almost
                         equal when they are connected together, large power transients will occur until the
                         generators stabilise at a common frequency. The frequencies of the two generators
                         must differ by a small amount so that the phase angles of the oncoming generator
                         will change slowly relative to the phase angles of the running system. The angles
                         between the voltages can be observed with suitable instrumentation, e.g., synchro-
                         scope, and the synchronising circuit breaker can be closed when the systems are
                         exactly in phase.
   48   49   50   51   52   53   54   55   56   57   58