Page 246 - Pipeline Rules of Thumb Handbook
P. 246

Corrosion/Coatings  233









                                                                                Figure 4. Structure of the mV drop method
                                                                                for AC.

















             Reference 1 provides specific data and a discussion of the  offset associated with nonlinear loads may have caused the
           likely effect of stray pickup. It is probably less than a fraction  problem.
           of an ampere of equivalent i i in clamps on a pipe in a common
           corridor with a three-phase transmission line having up to
                                                                   Personnel safety Gas and oil transmission pipelines are
           1,000A in the lines.
                                                                 frequently laid in a corridor adjacent to high-voltage trans-
                                                                 mission lines. There can be considerable current induced in
                                                                 pipe in such a corridor. This can be a hazard to both property
                    Uses of a clamp-on AC ammeter
                                                                 and personnel.
             Interference and fault location, corrosion control, and
           personnel safety are important considerations when using
                                                                                  mV drop method
           clamp-on ammeters.
                                                                   Figure 4 illustrates the mV drop method. Here, the pipe
             Interference and fault location A corrosion control pro-
                                                                 itself is used as a shunt for measuring AC flowing in the pipe.
           fessional may find that there is direct current (DC) interfer-
                                                                 This is similar to the method that is used for measuring DC
           ence flowing in a line but does not know where it is coming
                                                                 flowing in the pipe, except that the mV potential is measured
           from. The wave form or audio tone of the interfering current
                                                                 using an AC millivoltmeter.
           is a clue to the probable source.
                                                                   If the resistance of the pipe over the span is 0.5mW and
             A 24-h record of i i will likely show a constant interference
                                                                 the mV meter reads 1.1mV, one may at first think that the
           current if it is from a foreign CP system. Recurring peaks and
                                                                 pipe current is 2.2A. This would be correct for DC, but there
           valleys can point to interference from an electrified railroad.
                                                                 is inductance—skin effect and stray pickup need to be
           A 25-Hz current, for example, has been observed on a
                                                                 considered.
           pipeline near an AC-operated railroad.
             Corrosion control Gummow has written about corrosion
                                       2
           resulting from alternating current. He notes that studies in              Inductance
           the mid 1980s found that, above a certain miminum level of
           AC current density, normal levels of CP will not provide  If the reactance of the ~100-ft (30.5-m) measurement span
           acceptable levels of AC corrosion control.            is 0.3mW at 60Hz, this adds in quadrature to the 0.5mW resis-
             There are also concerns over corrosion problems in copper  tance (R) so the impedance (Z) becomes 0.58mW—a 16%
           and steel freshwater piping systems associated with unwanted  increase. At 60Hz, skin effect may add even more Z.
           AC caused by grounding practices. It was reported that in   At 120Hz, the major ripple frequency for most full-wave
           a large hospital, pipe replacements were required after only  rectifiers, the reactance is likely doubled to 0.6mW, so Z
           2 to 3 years because AC current was found on the piping;   increases to 0.78mW, a 56% increase. Skin effect is also
           a pipe current  >75mArms was deemed a hazard. The DC  greater.
   241   242   243   244   245   246   247   248   249   250   251