Page 150 - Power Quality in Electrical Systems
P. 150

132   Chapter Nine


        Alternate                                        CB
          line
                                                                   To load
                                                         CB



                                                         Diesel
            Line    CB       M        G
                                                        engine
                            Motor starter
                                              Flywheel  Eddy current
                                                          clutch
        Figure 9.2a MG UPS with flywheel, clutch, and diesel engine [9.1].


        500 kVA for the FAA Air Route Air Traffic Control Centers. The overall
                                                                1
        MTBF requirement was 100,000 h and the MTTR was 1h [9.4]. The indi-
        vidual modules were assumed to have an MTBF of 1100 h. Modern UPS
        modules are considerably more reliable. The concept of uninterruptible
        system availability is described in Chapter 8.
          The major change in the design of inverters since their inception for
        UPSs is the replacement of the silicon controlled rectifiers (SCRs) as the
        switch devices by IGBTs. The SCRs require forced commutation to turn
        off the current—that is, to open the switch. The IGBTs are controlled
        by the gate voltage. The forced commutation for SCRs required addi-
        tional circuits and operations that increased the failure rates and
        reduced the reliability of the inverters. Furthermore, the IGBTs can be
        switched much faster than SCRs, which enabled pulse-width modula-
        tion (PWM)—in other words, the voltage and current waveform shap-
        ing to be used.
          An early concept of UPS that preceded the SCR is shown in Figure 9.2a.
        It was a rotary machine set consisting of a diesel engine, clutch, elec-
        tric motor, flywheel, and generator [9.1]. When utility power was avail-
        able, the motor drove the generator. When utility power failed, the
        engine would be started while the flywheel and the generator slowed.
        At a certain speed, the clutch was engaged so the engine could drive
        the generator to restore and maintain its synchronous speed. A motor-
        generator which is a UPS, but employs batteries to provide energy
        when utility power fails, is shown in Figure 9.2b.





          1
           MTBF   Mean time between failures. MTTR   Mean time to repair.
   145   146   147   148   149   150   151   152   153   154   155