Page 151 - Power Quality in Electrical Systems
P. 151

Uninterruptible Power Supplies  133


                                                ML
        Alternate
          line
                                     Thyristor
                                      switch





            Line       Rectifier     Inverter          M    G    To load
                                                 MI     MG set
                                              contactors


                              Battery


                                      (b)
        Figure 9.2b MG UPS with load-commutated inverter and battery [9.1].



        Types of UPS Equipment
        Commercially available UPS equipment can be categorized into the fol-
        lowing types, depending upon the manufacturer and the application.
        ■ Output Ratings
          ■ Power: 1 kVA single-phase to 1000 kVA three-phase per module
          ■ Voltage: 120 V single-phase to 208 V/120 V or 480 V three-phase
        ■ Design
          ■ Double: Conversion or Delta
          ■ Inverter: Power transistors, IGBTs. Pulse-width modulated with
            output filter
          ■ Battery Charger: Input rectifier or separate charger
          ■ By-pass Circuit: Thyristors or IGBTs
          ■ Maintenance By-pass: Circuit breaker
        ■ Energy Storage
          ■ Batteries: Flooded, VLRA (value regulated lead acid)
          ■ Flywheels
          ■ Fuel cells
        ■ Typical Run Time
          ■ Batteries: 5 to 20 minutes at full load
          ■ Flywheels: 15 seconds, enough time to start E/G set
          ■ Fuel cells: 8 hours
   146   147   148   149   150   151   152   153   154   155   156