Page 156 - Practical Power System and Protective Relays Commissioning
P. 156

Gas Insulated System Substations Chapter | 14  155


             equipment it should be left to stabilize for several hours to ensure the density
             is correct.
                The truck system consists of the following components:
               Oil-free suction pump for recovery of SF 6 .
               Vacuum pump for evacuation of air.
               Operating indication of the most important process parameters in a screen
                panel.
               Evaporator.
               Particle filter.
               Dry filter.
               Pressure and vacuum units.
               Weighing scales for SF 6 bottles.
               Long storage connecting hose.
                Note: Before any gas handling is performed it is important to ensure that
             the equipment has been properly isolated from energized electrical sources.