Page 232 - Practical Power System and Protective Relays Commissioning
P. 232

232  Practical Power System and Protective Relays Commissioning


               Dead time of autoreclosing relay:
               The time between the autoreclosing scheme being energized and the
            operation of the contacts which energize the circuit-breaking closing circuit.
            On all but instantaneous or very high-speed reclosing schemes, this time is
            virtually the same as the CB dead time.
               Dead time of CB:
               The time between the fault arc being extinguished and the CB contacts
            remaking.
               High-speed reclosing scheme:
               A scheme whereby a CB is automatically reclosed within 1 second after a
            fault trip operation.
               Lock-out of autoreclosing relay:
               A feature of the autoreclosing scheme which, after tripping of the CB,
            prevents further automatic reclosing.
               Delay autoreclosing (DAR) scheme:
               A scheme whereby the automatic reclosing of the CB following a fault
            trip operation is delayed for a time in excess of 1 second.
               Multishot reclosing:
               An operation sequence providing more than one reclosing operation on a
            given fault before lock-out of the CB occurs.
               Opening time of a CB:
               The time from the energizing of the trip coil until the fault arc is
            extinguished.
               Operation time of protection:
               The time from the inception of the fault to the closing of the tripping
            contacts of the relay. Where a separate tripping relay is employed, its open-
            ing time is included.
               Reclaim time:
               The time following a successful closing operation, measured from the instant
            the autoreclose relay makes contact, which must elapse before the autoreclose
            relay will initiate a reclosing sequence in the event of a further fault incident.
               Single shot autoreclosing:
               An operation sequence providing only one reclosing operation, lock-out
            of the CB occurring on a subsequent tripping.
               Refer to Figs. 18.6.30 and 18.6.31 for an autoreclosing cycle for transient
            and permanent faults.



            18.6.11.2 Autoreclosing for Transmission Lines
            For 500-kV lines, only lines to ground faults are candidates to allow high-
            speed autoreclose.
               High-speed auto reclosing (unsupervised) should be applied where it sup-
            ports system stability or if load continuity is a concern.
   227   228   229   230   231   232   233   234   235   236   237