Page 230 - Practical Power System and Protective Relays Commissioning
P. 230

230  Practical Power System and Protective Relays Commissioning


            18.6.9 SWITCH ON TO FAULT FEATURE IN DISTANCE RELAY
            This feature in distance protection is activated after manual closure of a CB
            and is designed to bypass the distance relay measuring element and switched
            to a high-speed overcurrent function in case there is a close-up three-phase
            fault near the relay in the local busbar of the relay, as in practice
            maintenance people forgot the local three-phase earthing on the line under
            maintenance inside the substation, as in this case the relay voltage will be
            near zero and the fault is a three-phase close-up fault.
               The criteria for detecting the switch to fault (SOTF) condition are by
            voltage-level detector and current-level detector, for example, setting these
            two detectors is as follows:
               V ph , 75% V n and I ph . 5% In, as V n is the nominal voltage and I n is the
            nominal current of the system the SOTF will be energized for about 500 ms
            and then reset after this time. If the conditions above are detected during
            manual closure of the breaker during this time the SOTF will trip the line
            instantaneously.


            18.6.10 STUB PROTECTION FUNCTION

            There are short sections of the current path within a substation that are not
            properly protected by the main protection system. These sections are called
            stubs or blind spots protection or minimum zone protection, and they are
            usually between the CB and the CT. The main protection system measures
            the current of the CT and, if a fault is detected, a command is generated to
            open the CB. If, however, the fault is between the CB and the CT, then
            opening the CB cannot clear the fault; it is fed via the CT from the other
            side of the protected object. This location is within the back-up zone of the
            other side protection and, accordingly, it is cleared by a considerable time
            delay. The task of the stub protection function is to detect the fault current in
            the open state of the CB and to generate a quick trip command to the
            other side CB. Another usual application is in the one-and-a-half CB
            arrangement. Here the CTs are located either before or after the CBs.
            Additionally, the VT is either on the bus side or on the line side of the
            isolator. In the last case, the stub is also the section between the CBs and
            the open line isolator, since if a fault occurs in this section, the detected
            voltage is independent of the fault; it is unchanged and cannot be applied
            for the distance protection. The stub protection function is basically a
            high-speed overcurrent protection function that is enabled by the open
            state of a CB or may be an isolator. If any of the phase currents is above
            the start current and the binary status signal activates the operation, then
            after a user-defined time delay the function generates a trip command.
            The function can be disabled by programming the blocking signal in new
   225   226   227   228   229   230   231   232   233   234   235