Page 226 - Practical Power System and Protective Relays Commissioning
P. 226

226  Practical Power System and Protective Relays Commissioning























            FIGURE 18.6.26 Blocking overreach transfer scheme.

              At end A, fault F 1 will be seen by Z 2 A if a received blocking signal is
               received from remote end B. This means the relay will not trip on F 1 , but
               if the fault is on the line side as F 2 no signal will be received from end B
               to block operation of relay at end A, then the relay at end A Zone 2 will
               trip instantaneously for fault F 2 (refer to Fig. 18.6.27 for the scheme trip
               logic).






















            FIGURE 18.6.27 permissive overreach transfer trip blocking scheme.

            18.6.6 DISTANCE RELAY INPUTS FOR CORRECT
            MEASUREMENT OF DIFFERENT TYPES OF FAULTS
            The distance relay to measure the correct value of impedance should have
            the correct inputs as follows:
   221   222   223   224   225   226   227   228   229   230   231