Page 223 - Practical Power System and Protective Relays Commissioning
P. 223

Protection Relays Chapter | 18  223




















             FIGURE 18.6.19 Trip logic of the permissive underreach transfer trip scheme.

             18.6.5.3 Permissive Overreach Scheme (Directional
             Comparison Scheme)
             In this scheme Zone 2 is set to 120% of the transmission line, as shown in
             Fig. 18.6.20.

               For a fault F, the relay at end B will see the fault and send the POTT sig-
                nal to end A.












             FIGURE 18.6.20 Permissive overreach transfer trip scheme.

               At end A, the relay Zone 2 will see the fault F and send the POTT signal
                to end B if Zone 2 of relay A sees the fault F and receives a POTT signal
                from remote end B then the relay A will trip instantaneously, if not the
                relay will trip in Zone 2 time (500 ms) (refer to Fig. 18.6.21 for POTT
                logic).


             18.6.5.4 Zone Extension Scheme

             In this scheme, the relay has two settings for Zone 1, The first is the basic
             setting at 80% of Z L and the second is Zone 1 extension set to 120% Z L ,as
             shown in Fig. 18.6.22.
                For a fault F, the normal setting of relay at end A is Z 1 extension, the
             relay A will trip on fault F. The autoreclose relay will reset the setting of the
   218   219   220   221   222   223   224   225   226   227   228