Page 229 - Root Cause Failure Analysis
P. 229

Control Valves    217





























                    Figure 17-1 6 Actuator-controlled valve schematics.





                    return ensures that the valve is in its neutral (i.e., right) position when the solenoid is
                    de-energized.

                    The bottom schematic represents a double-solenoid, detented, two-position valve.
                    The solenoids are used  to shift the  valve between  its two positions. A  secondary
                    device, called a detent, is used to hold the valve in its last position until the alternate
                    solenoid is energized. Detent configuration varies with the valve type and manufac-
                    turer. However, all configurations prevent the valve’s control device from moving
                    until a strong force, such as that provided by  the solenoid, overcomes its  locking
                    force.

                    Actuators
                    As with process-control valves, actuators used to control fluid-power valves have  a
                    fundamental influence on performance. The actuators must provide positive, real-time
                    response to control inputs. The primary types of actuators used to control fluid-power
                    valves are mechanical, pilot, and solenoid.

                    Mechanical  The use of  manually controlled mechanical valves is limited in both
                    pneumatic and hydraulic circuits. Generally, this type of actuator is used only on
                    isolation valves that  are activated when  the circuit or  fluid-power system is  shut
                    down for repair or when direct operator input is required to operate one of the sys-
                    tem components.
   224   225   226   227   228   229   230   231   232   233   234