Page 98 - Root Cause Failure Analysis
P. 98

Pumps        89

                   Each time the flow is interrupted by  a change of  direction, a restriction caused by
                   valving, or a change in pipe diameter, the flow resistance of  the piping increases
                   substantially. The  actual  amount  of  this  increase  depends  on  the  nature  of  the
                   restriction. For example, a short-radius elbow creates much more resistance than a
                   long-radius elbow, a ball valve’s resistance is much greater than a gate valve’s, and
                   the resistance from a pipe-size reduction of  4 in. will be greater than for a  1-in.
                   reduction. Reference tables are available in hydraulics handbooks that provide the
                   relative values for each of the major sources of friction loss. As in the friction tables
                   mentioned previously, these tables often provide the friction loss as equivalent runs
                   of straight pipe.

                   In some cases, friction losses are difficult to quantify. If  the pumped liquid is deliv-
                   ered to an intermediate storage tank, the configuration of the tank’s inlet determines if
                   it adds to the system pressure. If  the inlet is on or near the top, the tank will add no
                   back pressure. However, if the inlet is below the normal liquid level, the total height
                   of liquid above the inlet must be added to the total system head.

                   In applications where the liquid is used directly by one or more system components,
                   the contribution of these components to the total system head may be difficult to cal-
                   culate. In some cases, the vendor’s manual or the original design documentation will
                   provide this information. If  these data are not available, then the friction losses and
                   back  pressure  need  to be  measured or  an overcapacity pump  selected for service
                   based on a conservative estimate.


                   Operating Methods
                   Normally, little consideration is given to operating practices for centrifugal pumps.
                   However, some critical practices must be followed, such as using proper startup pro-
                   cedures, using proper bypass operations, and operating under stable conditions.

                   Startup Procedures
                   Centrifugal pumps always should be started with the discharge valve closed. As soon
                   as the pump is activated, the valve should be opened slowly to its full-open position.

                   The only exception to this rule is when there is positive back pressure on the pump at
                   startup. Without adequate back pressure, the pump will absorb a substantial torsional
                   load during the initial startup sequence. The normal tendency is to overspeed because
                   there is no resistance on the impeller.

                   Bypass Operation

                   Many pump applications include a bypass loop intended to prevent deadheading (i.e.,
                   pumping against a closed discharge). Most bypass loops consist of a metered orifice
                   inserted in the bypass piping to permit a minimal flow of liquid. In many cases, the
                   flow permitted by these metered orifices is not sufficient to dissipate the heat gener-
                   ated by the pump or to permit stable pump operation.
   93   94   95   96   97   98   99   100   101   102   103