Page 488 - Sensors and Control Systems in Manufacturing
P. 488

FIGURE 9.2  Dual-level control.           Communications     441

                          and OFF when the maximum level has been reached:

                                                    Max = 1
                                                    Min = 1

                             If the level is between the two levels

                                                    Max = 0
                                                    Min = 1
                          the motor maintains the current status.
                             The constant level is disturbed by varying the bleed-off valve.
                          These requirements are shown in a fact table, where P represents a cur-
                          rent status and PN represents the required pump status (Table 9.1).


                                       Max     Min    P     Port   PN
                                       0       0      0     I      1
                                       0       0      1     I      1
                                       0       1      0     I      0
                                       0       1      1     I      1
                                       1       1      0     I      0
                                       1       1      1     I      0

                                      TABLE 9.1  Fact Table