Page 103 - Sustainable On-Site CHP Systems Design, Construction, and Operations
P. 103

Thermal Design for CHP     81


                    25,000



                    20,000
                   Peak hourly load (tons)  15,000





                    10,000


                     5,000



                        0
                         0    1000   2000  3000   4000  5000  6000   7000  8000
                                                Hours per year
             FIGURE 4-8  Cooling load duration curve. (Courtesy of Integrated CHP Systems Corporation.)



             electric load if the chillers were based on electric motor drive vapor compressors. This
             example can apply any CHP configuration with a T/E  ratio value of 0.5 ton/kW such
                                                           C
             as a combustion turbine.
                If the facility does have a heating need, then we can combine the heating and cooling
             loads to increase the thermal output of the system. In this case we would only need to
             address the cooling loads during the summer which would then provide us with a base
             load of over 2000 tons for a 100 percent load factor during the 4000 hours of the summer.
             Now the T/E  ratio becomes 1 ton/kW so we could consider a combustion turbine with
                        C
             duct burner to meet this load.
                While most facilities have 15-minute interval data available for power usage, most
             do not have similar data available for thermal loads. Considering the investment
             required to install a CHP plant, it is advisable to install flow meters and temperature
             sensors to measure and record thermal loads at hourly intervals if these devices are not
             already installed. The cost to accurately measure thermal loads is far outweighed by the
             cost savings from a well-designed CHP plant.
                In addition to calculating the base load for the system, we also need to understand
             the type and quality of the load. As noted, thermal loads take many forms from steam,
             hot water, and hot air for heating to chilled water, refrigeration, and dehumidification
             for cooling. The supply gage pressure or the temperature requirement of the supply
             and return water to load at the interconnection point of the facility distribution system
             need to be incorporated to accurately model the system’s thermal performance.
                If the load requirements do not match the output or quality of the CHP system there
             may still be ways to integrate the two systems through load optimization. Facilities that
             require very low temperature refrigeration for cold storage, for example, can either use
             ammonia/water absorption or alternatively can use a LiBr absorber to cool the condenser
             section of a centrifugal chiller to allow it reach the lower temperatures. This way the
   98   99   100   101   102   103   104   105   106   107   108